Request a Quote
Home Products Solutions About Us Resource Hub
Request a Quote
Resource Hub

HVAC Calculation

How to Calculate Exhaust CFM for Commercial Kitchens

Step-by-step CFM sizing using NFPA 96 hood capture velocity and equipment heat load. Includes a worked example for a 12 ft canopy hood over a 6-burner range.

Sizing exhaust airflow for a commercial kitchen hood is one of the most consequential decisions in any foodservice HVAC design. Undersize it and you get smoke escape, code violations and complaints from staff. Oversize it and the building loses thousands in conditioned air every month, plus the makeup-air system fights the hood instead of helping it.

This guide walks through the two methods accepted by NFPA 96 and IMC 507 — the perimeter method and the heat-load method — and shows how to reconcile them on a real project.

1. Define the cooking equipment line

Before any calculation, list every appliance that will sit under the hood and classify it by duty: light (steam tables, ovens), medium (fryers, ranges), heavy (charbroilers, woks) or extra-heavy (solid-fuel charbroilers). The duty class drives both the minimum capture velocity and the hood overhang requirement.

2. Apply the perimeter (hood-front) method

For a Type I canopy hood, the baseline formula is CFM = L (ft) × Q (CFM per linear foot), where Q depends on duty class:

Duty Class Wall-Mounted Q (CFM/ft) Island Q (CFM/ft)
Light 200 250
Medium 300 400
Heavy 400 550
Extra-Heavy 550 700

Worked example: a 12 ft wall-mounted canopy hood over a 6-burner range plus a flat-top griddle is classified medium-duty. Required exhaust = 12 × 300 = 3,600 CFM.

3. Cross-check with the heat-load method

Sum the rated sensible heat output of every appliance under the hood (manufacturer cut sheets give this in BTU/h). Convert to CFM using CFM = Q_sensible / (1.08 × ΔT), where ΔT is the temperature rise across the hood (typically 100°F for medium-duty).

If the heat-load result is more than 15% higher than the perimeter result, defer to the larger value. If it is lower, use the perimeter number — capture velocity is the binding constraint, not pure thermal removal.

4. Add the makeup-air balance

Code requires makeup air at 80–90% of the exhaust rate, introduced low-velocity (≤75 FPM at the cooking line) so it does not disturb capture. The remaining 10–20% comes from the building HVAC as transfer air, which keeps the kitchen at slight negative pressure relative to the dining room.

Common mistake: matching makeup air 1:1 to exhaust. The kitchen then goes positive, smoke spills into the dining room, and the hood loses 15–20% of its effective capture rate.

5. Final fan selection

Add a 10% safety margin to the design CFM and select an upblast roof exhaust fan with sufficient static pressure to overcome the duct run, grease filter loss (0.4–0.6 in. w.c. when loaded) and termination loss. For our 3,600 CFM example, target 4,000 CFM at 1.0–1.25 in. w.c. SP — a TTTIGER UE-450-EC or equivalent will sit comfortably in its efficient operating band.

Related Articles

EC vs AC Fans: Cost-Benefit Analysis for Indoor Farming
Energy Efficiency

EC vs AC Fans: Cost-Benefit Analysis for Indoor Farming

Three-year TCO model comparing EC and AC fans across a 2,000 m² hydroponics facility. Payback typically lands inside 18 months at $0.12/kWh.

Installation Guide: Inline Duct Fan Mounting in Tight Ceilings
Installation Guide

Installation Guide: Inline Duct Fan Mounting in Tight Ceilings

Vibration isolators, service-loop slack, ducting alignment and access-panel placement for inline fans in <300 mm plenums.